Capacitor Contactors by LOVATO Electric GmbH

Product inquiry

Contactors for power factor correction with AC control circuit

Ambient operating temperature: ≤50°C.
For ambient temperatures higher than 50°C and up to 70°C, the maximum operating power values indicated in the table must be reduced by a percentage equal to the difference between the operating ambient temperature and 50°C.
E.g.: Using a BFK26 00 contactor at the ambient temperature of 60°C, the maximum operating power (at 400V) of the contactor will be equal to 20kvar – 10% = 18kvar.
Operating cycle: ≤120 cycles/h
Electrical life: ≥400,000 cycles.